EasyManua.ls Logo

Eaton EDR-5000 - Energy Counter; Global Parameters of the Energy Counter Module; Direct Commands of the Energy Counter Module

Eaton EDR-5000
1041 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Energy Counter
ECr
Global Parameters of the Energy Counter Module
Parameter Description Setting range Default Menu path
Power Units Power Units Power Auto Scaling,
kW/kVAr/kVA,
MW/MVAr/MVA,
GW/GVAr/GVA
Power Auto
Scaling
[Operation
/General Settings]
Energy Units Energy Units Energy Auto Sca-
ling,
kWh/kVArh/kVAh,
MWh/MVArh/MVAh,
GWh/GVArh/GVAh
MWh/MVArh/MVA
h
[Operation
/General Settings]
Direct Commands of the Energy Counter Module
Parameter Description Setting range Default Menu path
Res all Energy Cr Reset of all Energy Counters Inactive,
Active
Inactive [Operation
/Reset]
www.eaton.com 169

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals