EasyManua.ls Logo

Eaton EDR-5000 - Direct Commands of the System Module

Eaton EDR-5000
1041 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Direct Commands of the System Module
Parameter Description Setting range Default Menu path
Ack RO LED Comm
TCmd
Reset the Relay Outputs, LEDs, Communication, and the
Trip Command.
Inactive,
Active
Inactive [Operation
/Reset]
Ack LED All acknowledgeable LEDs will be acknowledged. Inactive,
Active
Inactive [Operation
/Reset]
Ack RO All acknowledgeable Relay Outputs will be
acknowledged.
Inactive,
Active
Inactive [Operation
/Reset]
Ack Comm Communication will be acknowledged. Inactive,
Active
Inactive [Operation
/Reset]
Reboot Rebooting the device. No,
Yes
No [Service
/General]
MaintMode
Manually
Arc Flash Reduction Maintenance Switch Mode: Manual
Activation of the Arc Flash Reduction Mode
Only available if: Maint Mode = Activation Manually
Maint Mode inacti-
ve,
Activation via
Comm,
Activation via DI,
Inactive,
Active
Inactive [Service
/MaintMode
Manually]
Program Mode
Bypass
Short-period bypass of the Program Mode. Inactive,
Active
Inactive [System Para
/General Settings]
CAUTION: Manually rebooting the device will release the Supervision
Contact.
www.eaton.com 248