EDR-5000 IM02602007E
Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High) 4.75 to 5.25 Vdc
Output voltage (Low) 0.0 to +0.5 Vdc
Zone In:
Nominal input voltage +5 Vdc
Max. input voltage +5.5 Vdc
Switching threshold ON min. 4.0 Vdc
Switching threshold OFF max. 1.5 Vdc
Galvanic isolation 2.5 kV ac (to ground and other IO)
Connection: Screw-type terminals (twisted pair)
RS485*
Master/Slave: Slave
Connection: 6 screw-clamping terminals RM 3.5 mm (138 MIL)
(terminating resistors internal)
The RS485 interface is realized via terminals. The communication cable has
to be shielded. The shielding has to be fixed at the screw that is marked
with the ground symbol (rear side of the device).
LWL-Module with ST connector*
Master/Slave: Slave
Connector: ST-Port
Compatible Fiber: 50/125 µm, 62,5/125 µm, 100/140 µm and 200 µm HCS
Wavelength
820 nm
Minimum Optical Input Power: -24,0 dBm
Minimum Optical Output Power: -19.8 dBm with 50/125 µm Fiber
-16,0 dBm with 62,5/125 µm Fiber
-12,5 dBm with 100/145 µm Fiber
-8,5 dBm with 200 µm HCS Fiber
Maximum Link Length: 2.7 km (depending on link attenuation)
Please note: The transmission speed of the optical interfaces is limited to 3 MBaud for Profibus.
www.eaton.com 909