EDR-5000 IM02602007E
Programmable Logic at the Panel
WARNING improper use of logic equations might result in personal injury
or damage the electrical equipment.
Do not use logic equations unless the User can ensure the safe
functionality.
How to configure a logic equation?
Within the Device Planning, set the number of required Logic Equations.
Call up the [Logic] menu.
Select a Logic Equation that is to be set.
Set the Input Signals (where necessary, invert them).
If required, configure the timer (»
On delay«
and »
Off delay«
).
If the latched output signal is used, assign a reset signal to the reset input.
Within the »status display«, the User can check the status of the logical inputs and outputs of the logic equation.
In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of
descending sequences (Please refer to the Cascading Logical Outputs section).
By means of the Status Display [Operation/Status Display], the logical states can be verified.
www.eaton.com 865