Global Protection Parameter of the Demand Management
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [SysA
/General Settings]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
1..n, Assignment
List
-.- [SysA
/General Settings]
Alarm Alarm Inactive,
Active
Inactive [SysA
/Power
/Watt]
Threshold Threshold (to be entered as primary value) 1 - 40000000kW 10000kW [SysA
/Power
/Watt]
t-Delay Tripping Delay 0 - 60min 0min [SysA
/Power
/Watt]
Alarm Alarm Inactive,
Active
Inactive [SysA
/Power
/VAr]
Threshold Threshold (to be entered as primary value) 1 - 40000000kVAr 10000kVAr [SysA
/Power
/VAr]
t-Delay Tripping Delay 0 - 60min 0min [SysA
/Power
/VAr]
Alarm Alarm Inactive,
Active
Inactive [SysA
/Power
/VA]