EDR-5000 IM02602007E
Control Parameters
Direct commands of the Control Module
Parameter Description Setting range Default Menu path
Switching Authority Switching Authority None,
Local,
Remote,
Local and Remote
Local [Control
/General Settings]
Signals of the Control Module
Signal Description
Local Switching Authority: Local
Remote Switching Authority: Remote
SG Indeterm Minimum one Switchgear is moving (Position cannot be determined).
SG Disturb Minimum one Switchgear is disturbed.
Counters of the Control Module
Parameter Description
CES SAuthority Command Execution Supervision: Switching Command not executed. No switching authority.
CES DoubleOperating Command Execution Supervision: A second switch command is in conflict with a pending one.
No. of rej. Com No. of rej. Com because Locked by ParaSystem
www.eaton.com 443