EDR-5000 IM02602007E
Name Description
CT.IC RMS Measured value: Phase current (RMS)
CT.IX meas RMS Measured value (measured): IX (RMS)
CT.IR calc RMS Measured value (calculated): IR (RMS)
CT.I0 Fund. Measured value (calculated): Zero current (Fundamental)
CT.I1 Fund. Measured value (calculated): Positive phase sequence current (Fundamental)
CT.I2 Fund. Measured value (calculated): Unbalanced load current (Fundamental)
CT.%(I2/I1) Measured value (calculated): I2/I1, phase sequence will be taken into account automatically.
CT.IA avg RMS IA average value (RMS)
CT.IB avg RMS IB average value (RMS)
CT.IC avg RMS IC average value (RMS)
CT.IA THD Measured Value (Calculated): IA Total Harmonic Current
CT.IB THD Measured Value (Calculated): IB Total Harmonic Current
CT.IC THD Measured Value (Calculated): IC Total Harmonic Current
ECr.Syst VA Fund. Measured VAs (Fundamental)
ECr.Syst W Fund. Measured Watts. Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (Fundamental)
ECr.Syst VAr Fund. Measured VARs. Reactive power (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power)
(Fundamental)
ECr.Syst W 1 Measured Watts. Active power in positive sequence system (P- = Fed Active Power, P+ = Consumpted Active
Power)
ECr.Syst VAr 1 Measured VARs. Reactive power in positive sequence system (Q- = Fed Reactive Power, Q+ = Consumpted
Reactive Power)
ECr.Syst VA RMS Measured VAs (RMS)
ECr.Syst W RMS Measured Watts. Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS)
ECr.Disp PF Measured Value (Calculated): 55D - Displacement Power Factor: Sign Convention: sign(PF) = sign(Syst W)
ECr.Apt PF Measured Value (Calculated): 55A - Apparent Power Factor: Sign Convention: sign(PF) = sign(Syst W)
ECr.VAh Net Net VA Hours
ECr.Wh Net Net Watt Hours
ECr.VArh Net Net VAr Hours
ECr.Wh Fwd Positive Active Power is consumed active energy
ECr.Wh Rev Negative Active Power (Fed Energy)
ECr.VArh Lag Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead Negative Reactive Power (Fed Energy)
www.eaton.com 224