EDR-5000 IM02602007E
Global Protection Parameters of the Breaker Wear Module
Parameter Description Setting range Default Menu path
Operations Alarm Service Alarm, too many Operations 1 - 100000 9999 [Control
/Bkr
/Bwear]
Isum Intr Alarm Alarm, the Sum (Limit) of interrupting currents has been
exceeded.
0.00 - 2000.00kA 100.00kA [Control
/Bkr
/Bwear]
Isum Intr ph Alm Alarm, the per hour Sum (Limit) of interrupting currents
has been exceeded.
0.00 - 2000.00kA 100.00kA [Control
/Bkr
/Bwear]
Bwear Curve Fc The Breaker Wear Curve defines the maximum allowed
CLOSE/OPEN cycles depending on the brake currents. If
the breaker maintenance curve is exceeded, an alarm
will be issued. The breaker maintenance curve is to be
taken from the technical data sheet of the breaker
manufactor. By means of the available points this curve
is to be replicated.
Inactive,
Active
Inactive [Control
/Bkr
/Bwear]
WearLevel Alarm Breaker Wear curve Alarm
Only available if:Bwear Curve Fc = Active
0.00 - 100.00% 80.00% [Control
/Bkr
/Bwear]
WearLevel Lockout Breaker Wear Curve Lockout Level
Only available if:Bwear Curve Fc = Active
0.00 - 100.00% 95.00% [Control
/Bkr
/Bwear]
Current1 Interrupted Current Level #1
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 0.1kA [Control
/Bkr
/Bwear]
Count1 Open Counts Allowed #1
Only available if:Bwear Curve Fc = Active
1 - 32000 10000 [Control
/Bkr
/Bwear]
Current2 Interrupted Current Level #2
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 1.00kA [Control
/Bkr
/Bwear]
www.eaton.com 437