EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Current8 Interrupted Current Level #8
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 16.00kA [Control
/Bkr
/Bwear]
Count8 Open Counts Allowed #8
Only available if:Bwear Curve Fc = Active
1 - 32000 75 [Control
/Bkr
/Bwear]
Current9 Interrupted Current Level #9
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 20.00kA [Control
/Bkr
/Bwear]
Count9 Open Counts Allowed #9
Only available if:Bwear Curve Fc = Active
1 - 32000 45 [Control
/Bkr
/Bwear]
Current10 Interrupted Current Level #10
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 25.00kA [Control
/Bkr
/Bwear]
Count10 Open Counts Allowed #10
Only available if:Bwear Curve Fc = Active
1 - 32000 30 [Control
/Bkr
/Bwear]