EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para
/Global Prot Para
/I-Prot
/50R[1]]
AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para
/Global Prot Para
/I-Prot
/50R[1]]
Setting Group Parameters of the 50R/67R Ground Fault Protection
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Active [Protection Para
/<1..4>
/I-Prot
/50R[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/I-Prot
/50R[1]]
Rvs Blo Fc Activate (allow) or inactivate (disallow) reverse blocking
of the module/element. This parameter is only effective if
a signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/element are blocked that are parameterized
"Rvs Blo Fc = active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/I-Prot
/50R[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/I-Prot
/50R[1]]
www.eaton.com 516