EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Curve Shape
Characteristic IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
ANSI MINV [Protection Para
/<1..4>
/I-Prot
/51R[1]]
t-multiplier
Time multiplier/tripping characteristic factor. The setting
range depends on the selected tripping curve.
0.02 - 20.00 51R[1]: 1
51R[2]: 2
[Protection Para
/<1..4>
/I-Prot
/51R[1]]
Reset Mode
Reset Mode Instantaneous,
t-delay,
Calculated
Calculated [Protection Para
/<1..4>
/I-Prot
/51R[1]]
t-reset
Reset time for intermittent phase failures (INV
characteristics only)
Only available if:Reset Mode = t-delay
0.00 - 60.00s 0.00s [Protection Para
/<1..4>
/I-Prot
/51R[1]]