EDR-5000 IM02602007E
Description of the Functions and Features
Configurable protection functions to initiate the zone interlocking OUTPUT signal (start functions).
Remove zone interlocking OUTPUT signal immediately after detection of a breaker failure.
Reset time (about ten cycles - settable) to interrupt OUTPUT signal for durable trip signal.
Small trip delay (about three cycles – settable) to wait for downstream devices interlocking signals.
Zone interlocking trip signal only possible by absence of zone interlocking INPUT signals.
Configurable zone interlocking trip functions (protective functions serve as zone interlocking trip functions).
Zone interlocking trip function pickup and tripping characteristic adaption using adaptive settings controlled by the
zone interlocking input signals.
Device Planning Parameters of the Zone Interlocking
Parameter Description Options Default Menu path
Mode Mode Use Use [Device Planning]
www.eaton.com 530