Please be aware of the meaning of the two delay timers.
t load Off (Pickup Delay): After this time expires, the load is no longer diversified.
t Max Block (Release Delay): After the starting condition is fulfilled (e.g.: breaker
switched on manually), the “CLPU.enabled” signal will be issued for this time. That
means for the duration of this time, the tripping thresholds of the overcurrent
protection can be desensitized by means of adaptive parameters (please refer to the
Parameters section). This timer will be stopped if the current falls below 0.9 times of
the threshold of the load inrush detector and remains below 0.9 times of the threshold
for the duration of the settle time.