EasyManua.ls Logo

Eaton EDR-5000 - Page 580

Eaton EDR-5000
1041 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
15
Reclosing
If there is no other blocking or lockout conditions and the breaker is closed while the breaker reclosing supervision timer
is timing, the autoreclosure starts the »
t-Run2Ready«
timer and goes into the state: »T-RUN2READY«.
16
t-Run2Ready
Successful Autoreclosure:
While in »T-RUN2READY« state, if there is no other blocking or lockout conditions and no more faults detected within the
»
t-Run2Ready«
timer, the autoreclosure logic will leave the »RUN« state and goes back to the »READY« state. The flag
“successful” is set.
Unsuccessful Autoreclose:
If a fault is detected again (the shot-controlled initiate function is triggering) while »
t-Run2Ready«
timer is still timing, the
autoreclosure control again transfers to the »RUNNING« state. For a permanent fault, the process described before will
be repeated until all programmed shots were operated and the autoreclose process changes into the »LOCKOUT« state.
The flag “failed” is set.
www.eaton.com 580

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals