Setting Group Parameters of the Aux. Overvoltage Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
Pickup Vn refers to the rated secondary voltage of the aux VT.
Only available if: Device Planning: 59.Mode = V>
0.01 - 1.30Vn 59A[1]: 1.2Vn
59A[2]: 1.1Vn
[Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
t Tripping delay 0.00 - 300.00s 0.00s [Protection Para
/<1..4>
/Aux-V-Prot
/59A[1]]
www.eaton.com 632