EasyManua.ls Logo

Eaton EDR-5000 - Page 648

Eaton EDR-5000
1041 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Sync-check Override Conditions
If enabled the following conditions can override the sync-check function:
LBDL = Live Bus – Dead Line
DBLL = Dead Bus – Live Line
DBDL = Dead Bus – Dead Line
Also the sync-check function can be bypassed by an external source.
When the sync-check function is overridden or bypassed, synchronization
has to be secured by other synchronizing systems before breaker closing!
www.eaton.com 648

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals