EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
LOP Blo Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Unbalance-Prot
/47[1]]
States of the Inputs of the Voltage Unbalance Module
Name Description Assignment via
ExBlo1-I Module Input State: External Blocking1 [Protection Para
/Global Prot Para
/Unbalance-Prot
/47[1]]
ExBlo2-I Module Input State: External Blocking2 [Protection Para
/Global Prot Para
/Unbalance-Prot
/47[1]]
ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command [Protection Para
/Global Prot Para
/Unbalance-Prot
/47[1]]
Signals of the Voltage Unbalance Module (States of the Outputs)
Signal Description
Active Signal: Active
ExBlo Signal: External Blocking
Blo TripCmd Signal: Trip Command blocked
ExBlo TripCmd Signal: External Blocking of the Trip Command
Pickup Signal: Pickup Voltage Asymmetry
Trip Signal: Trip
TripCmd Signal: Trip Command
www.eaton.com 668