Parameter Description Setting range Default Menu path
Pickup Q< Under(load) Reactive Power Pickup Value. Monitoring
the minimum value of the reactive power. If it falls below
the set value, a condensator bank could be switched on.
Definition for Sn is as follows: Sn = 1.7321 * VT rating *
CT rating. The voltage is the line-to-line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Q<
0.003 - 10.000VAn 0.80VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Qr> Overload Reverse Reactive Power Pickup Value
Definition for Sn is as follows: Sn = 1.7321 * VT rating *
CT rating. The voltage is the line-to-line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Qr>
0.003 - 10.000VAn 0.020VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
Pickup Qr< Under Reverse Definition for Sn is as follows: Sn =
1.7321 * VT rating * CT rating. The voltage is the line-to-
line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Qr<
0.003 - 10.000VAn 0.80VAn [Protection Para
/<1..4>
/Power-Prot
/32V[1]]
t Tripping delay 0.00 - 1100.00s 0.01s [Protection Para
/<1..4>
/Power-Prot
/32V[1]]