Parameter Description Setting range Default Menu path
Q min QV Trigger for the Reactive Power (Positive Phase
Sequence System)
Only available if: QV-Method = Pure Reactive Power
Superv
0.01 - 0.20VAn 0.05VAn [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
t1-QV First timer. If this timer has elapsed, a trip signal will be
issued to the (local) energy resource.
0.00 - 2.00s 0.5s [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
t2-QV Second timer. If this timer is elapsed, the an trip signal
will be issued to the PCC (Point of Common Coupling)
0.00 - 4.00s 1.5s [Protection Para
/<1..4>
/Q->&V<
/Decoupling]
Input States of the Q->&V< Module
Name Description Assignment via
ExBlo1-I Module Input State: External Blocking1 [Protection Para
/Global Prot Para
/Q->&V<]
ExBlo2-I Module Input State: External Blocking2 [Protection Para
/Global Prot Para
/Q->&V<]