EDR-5000 IM02602007E
Device Planning Parameters of the Reconnection Module
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Do not use [Device Planning]
Global Protection Parameters of the Reconnection Module
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/ReCon
/General Settings]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/ReCon
/General Settings]
V Ext Release PCC Release Signal by the Point of Common Coupling. The
line-to-line voltage is greater than 95% of VN.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/ReCon
/General Settings]
PCC Fuse Fail VT Blocking if the fuse of a voltage transformer has tripped
at the PCC.
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/ReCon
/General Settings]
reconnected This signal indicates the state "reconnected" (mains
parallel).
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/ReCon
/General Settings]
Decoupling1 Decoupling signal that triggers the reclosure. Decoupling
Functions
-.- [Protection Para
/Global Prot Para
/ReCon
/Decoupling]