EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
f< Lower frequency limit for the reclosure (Restoration
Voltage)
40.00 - 69.90Hz 47.5Hz [Protection Para
/<1..4>
/ReCon
/Release Para]
f> Upper freqeuncy limit for the reclosure 40.00 - 69.90Hz 50.05Hz [Protection Para
/<1..4>
/ReCon
/Release Para]
t-Release Blo Time stage (delay) for the reclosure of the energy
resources. The Mains seddle time takes based on
exirience approx. 10 - 15 minutes.
0.00 - 3600.00s 600s [Protection Para
/<1..4>
/ReCon
/Release Para]
www.eaton.com 768