EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Power Angle
Trigger Phi-Power (Positive Phase Sequence System)
Only available if: UFLS-Method = Power Angle
Supervision
0 - 10° [Protection Para
/<1..4>
/UFLS
/LoadShedding]
P min
Minimum Value (threshold) for the Active Power
Only available if: UFLS-Method = Pure Active Power
Superv
0.01 - 0.10VAn 0.05VAn [Protection Para
/<1..4>
/UFLS
/LoadShedding]
f<
Underfrequency threshold 45.00 - 65.00Hz 49.00Hz [Protection Para
/<1..4>
/UFLS
/LoadShedding]
t-UFLS
Tripping delay time 0.00 - 300.00s 0.1s [Protection Para
/<1..4>
/UFLS
/LoadShedding]
www.eaton.com 800