EDR-5000 IM02602007E
Energy measurement*
Energy counter error 1.5% of measured energy or 1.5% Sn*1h
Power Measurement*
VA, W, VAr: <±1% of the measured value or 0.1% Sn (for fundamental)
<±2% of the measured value or 0.1% Sn (for RMS)
W 1, Var 1 (pos. sequence): ±2% of the measured value or 0.2% Sn
Power Factor Measurement*
PF: ±0.01 of measured power factor or 1°
I > 30% In and S >2% Sn
*)Tolerance at 0.8 … 1.2 x Vn (with Vn=100V) , |PF|>0.5, symmetrically feeded
Sn=1.73 * VT rating * CT rating
www.eaton.com 919