EDR-5000 IM02602007E
Name Description
CTS.ExBlo Signal: External Blocking
CTS.Pickup Signal: Pickup Current Transformer Measuring Circuit Supervision
CTS.ExBlo1-I Module Input State: External Blocking1
CTS.ExBlo2-I Module Input State: External Blocking2
LOP.Active Signal: Active
LOP.ExBlo Signal: External Blocking
LOP.Pickup Signal: Pickup Loss of Potential
LOP.LOP Blo Signal: Loss of Potential blocks other elements
LOP.ExBlo1-I Module Input State: External Blocking1
LOP.ExBlo2-I Module Input State: External Blocking2
AR.Active Signal: Active
AR.ExBlo Signal: External Blocking
AR.Standby Signal: Standby
AR.t-Man Close Blo Signal: AR blocked after breaker was switched on manually. This timer will be started if the breaker was
switched on manually. While this timer is running, AR cannot be started.
AR.Ready Signal: Ready to shoot
AR.Running Signal: Auto Reclosing Running
AR.t-dead Signal: Dead time between trip and reclosure attempt
AR.Bkr CLOSE Cmd Signal: Bkr. Switch ON (CLOSE) Command
AR.t-Run2Ready Signal: Examination Time: If the Breaker remains after a reclosure attempt (shot) for the duration of this timer
in the Closed position, the AR has been successful and the AR module returns into the ready state.
AR.Lock Signal: Auto Reclosure is locked out
AR.t-Reset Lockout Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout state will be delayed for this time
after the reset signal (e.g digital input or Scada) has been detected .
AR.Blo Signal: Auto Reclosure is blocked
AR.t-Blo Reset Signal: Delay Timer for resetting the AR blocking. The release (de-blocking) of the AR will be delayed for this
time, if there is no blocking signal anymore.
AR.successful Signal: Auto Reclosing successful
AR.failed Signal: Auto Reclosing Failure
AR.t-AR Supervision Signal: AR Supervision
AR.Pre Shot Pre Shot Control
AR.Shot 1 Shot Control
AR.Shot 2 Shot Control
AR.Shot 3 Shot Control
AR.Shot 4 Shot Control
AR.Shot 5 Shot Control
AR.Shot 6 Shot Control
AR.Service Alarm 1 Signal: AR - Service Alarm 1, too many switching operations
www.eaton.com 993