M-Max Series adjustable frequency drive
42 For more information visit: www.eaton.com
MN04020002E
February 2010
Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
V/Hz Characteristic Curve (continued)
P11.8 600 — Motor control
mode
0 = Frequency control (V/Hz)
1 = Speed control (vector)
0
P11.9 601 — Pulse frequency 1.5 – 16.0 kHz 6.0
P11.10 522 — Sine-wave filter 0 = Deactivated
1 = Enabled
0
Braking
P12.1 507 — DC braking,
current
0.2 x I
e
– 2 x I
e
I
e
P12.2 516 — DC braking,
braking time in
case of RUN
0.00 – 600.00s 0.00
P12.3 515 — DC braking,
start frequency
0.00 – 10.00 Hz 1.50
P12.4 508 — DC braking,
braking time in
case of STOP
0.00 – 600.00s 0.00
P12.5 504 — Brake chopper (only active and visible with braking
transistor installed)
0 = Deactivated
1 = Active in RUN
2 = Active in RUN and STOP
0
P12.6 1447 — Brake chopper,
switching
threshold
(only active and visible with braking
transistor installed)
0 – 870V
0
P12.7 1448 — External brake,
delay time,
opening
0.00 – 320.00s 0.20
P12.8 1449 — External brake,
frequency
threshold,
opening
0.00 – 320.00 Hz 1.50
P12.9 1450 — External brake,
frequency
threshold,
closing
0.00 – 320.00 Hz 1.50
P12.10 1451 — External brake,
frequency
threshold REV,
closing
0.00 – 320.00 Hz 1.50
P12.11 1452 — External brake,
current limit
0.00 – P7.2 A 0.00