M-Max Series adjustable frequency drive
MN04020002E
For more information visit: www.eaton.com 41
February 2010
Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
Fixed Frequencies (continued)
P10.4 126 ✓ Fixed frequency
FF3
0.00 – P6.4 Hz 20.00
P10.5 127 ✓ Fixed frequency
FF4
0.00 – P6.4 Hz 25.00
P10.6 128 ✓ Fixed frequency
FF5
0.00 – P6.4 Hz 30.00
P10.7 129 ✓ Fixed frequency
FF6
0.00 – P6.4 Hz 40.00
P10.8 130 ✓ Fixed frequency
FF7
0.00 – P6.4 Hz 50.00
P10.9 1436 ✓ Flow control 0 = Deactivated
1 = Program cycle, once
2 = Program cycle, continuous
3 = Program cycle, step by step
4 = Program cycle, continuous and step
by step
0
P10.10 1437 ✓ Flow control,
FWD/REV bit
0 – 255 0
P10.11 1438 ✓ Set time for FF0 0 – 10000s 0
P10.12 1439 ✓ Set time for FF1 0 – 10000s 0
P10.13 1440 ✓ Set time for FF2 0 – 10000s 0
P10.14 1441 ✓ Set time for FF3 0 – 10000s 0
P10.15 1442 ✓ Set time for FF4 0 – 10000s 0
P10.16 1443 ✓ Set time for FF5 0 – 10000s 0
P10.17 1444 ✓ Set time for FF6 0 – 10000s 0
P10.18 1445 ✓ Set time for FF7 0 – 10000s 0
V/Hz Characteristic Curve
P11.1 108 — V/Hz
characteristic
curve
0 = Linear
1 = Squared
2 = Configurable
0
P11.2 602 — Cut-off frequency 30.00 – 320.00 Hz 60
P11.3 603 — Output voltage 10.00 – 200.00% of nominal motor
voltage (P6.5)
100.00
P11.4 604 — V/Hz
characteristic
curve, mean
frequency value
0.00 – P11.2 Hz 60
P11.5 605 —
V/Hz characteristic
curve, mean
voltage value
0.00 – P11.3% 100.00
P11.6 606 — Output voltage at
zero frequency
0.00 – 40.00 % 0.00
P11.7 109 — Torque increase 0 = Deactivated
1 = Enabled
0