M-Max Series adjustable frequency drive
40 For more information visit: www.eaton.com
MN04020002E
February 2010
Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
PID Controller (continued)
P9.6 334 — PID controller,
actual value
0 = Field bus (option)
1 = AI1
2 = AI2
2
P9.7 336 — PID controller,
actual value
limiting,
minimum
0.0 – 100.0% 0.0
P9.8 337 — PID controller,
actual value
limiting,
maximum
0.0 – 100.0% 100.0
P9.9 340 — PID controller,
controller
deviation
0 = not inverted
1 = inverted
0
P9.10 132 — PID controller,
D rate time
0.00 – 10.0s 0.00
P9.11 1431 — PID controller,
output filter,
delay time
0.00 – 10.0s 0.0
P9.12 1016 — Sleep mode,
frequency
0.00 – P6.4 Hz 0.00
P9.13 1018 — Sleep mode,
wake-up
frequency
0.0 – 100.0% 25.0
P9.14 1017 — Sleep mode,
delay time
0 – 3600s 30
P9.15 1433 — Hysteresis,
upper threshold
0.0 – 100.0% 0.0
P9.16 1434 — Hysteresis,
lower threshold
0.0 – 100.0% 0.0
P9.17 1435 — PID controller,
max. system
derivation
0.0 – 100.0% 3.0
P9.18 1475 — PID controller,
reference value
scaling
0.1 – 32.7 1.0
P9.19 1476 — PID controller,
process value
scaling
0.1 – 32.7 1.0
Fixed Frequencies
P10.1 124 ✓ Fixed frequency
FF0
0.00 – P6.4 Hz 5.00
P10.2 105 ✓ Fixed frequency
FF1
0.00 – P6.4 Hz 10.00
P10.3 106 ✓ Fixed frequency
FF2
0.00 – P6.4 Hz 15.00