M-Max Series adjustable frequency drive
MN04020002E
For more information visit: www.eaton.com 39
February 2010
Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
Protective Functions
P8.1 700 — 4 mA reference
value error
0 = Deactivated
1 = Warning
2 = Error, stop according to P6.8
1
P8.3 703 — Earth-fault
monitoring
Like P8.1 2
P8.4 709 — Stall protection Like P8.1 0
P8.5 713 — Underload
protection
Like P8.1 0
P8.6 704 — Motor,
temperature
protection
Like P8.1 0
P8.7 705 — Motor, ambient
temperature
-20 – +100ºC 40
P8.8 706 — Motor, cooling
factor at zero
frequency
0.0 – 150% 40
P8.9 707 — Motor,
thermal time
constant
1 – 200 min 45
P8.10 1430 — 4 mA reference
value error
0.0 – 10.0s 0.5
P8.11 1473 — Thermistor fault,
response
Like P8.1 2
P8.12 714 — Underload,
load curve at
rated frequency
10.0 – 150% 50.0
P8.13 715 — Underload,
load curve at
frequency = 0
10.0 – 150% 10.0
PID Controller
P9.1 163 — PID controller 0 = Deactivated
1 = to drive control
2 = for external application
0
P9.2 118 — PID controllers,
P gain
0.0 – 1000.0% 100.0
P9.3 119 — PID controller,
I time
0.00 – 320.00s 10.00
P9.4 167 — PID controller,
Keypad
reference
0.0 – 100.0% 0.0
P9.5 332 — PI controller,
set point source
0 = Keypad (P9.4)
1 = Field bus (option)
2 = AI1
3 = AI2
0