Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
Second Parameter Set (continued)
P14.6 1349 Motor[2], rated
frequency
30 – 320 Hz
( Motor rating plate)
60
P14.7 1343 Minimum
frequency [2]
0.00 – P6.4 Hz 0.00
P14.8 1344 Maximum
frequency [2]
P6.3 – 320.00 Hz 60
P14.9 1345 Acceleration
time [2]
0.1 – 3000s 3.0
P14.10 1346 Deceleration
time [2]
0.1 – 3000s 3.0
P14.11 1355 V/Hz
characteristic
curve [2]
0 = Linear
1 = Quadratic
2 = Configurable
0
P14.12 1354 Torque boost [2] 0 = Deactivated
1 = Enabled
0
P14.13 1353 Overload
protection [2]
Like P8.1 0
P14.14 1469 Motor [2],
ambient
temperature
-20 – +100 ºC 40
P14.15 1470 Cooling factor at
zero frequency
[2]
0.0 – 150% 40.0
P14.16 1471 Motor
temperature time
constant [2]
1 – 200 min 45
System Parameters
Hardware and Software Information
S1.1 833 Software-
Package
—0
S1.2 834 Software
version,
power section
—0
S1.3 835 Software
version,
control part
—0
S1.4 836 Firmware,
interface
—0
S1.5 837 Application, ID 0
S1.6 838 Application,
revision
—0
S1.7 839 System load % 0