M-Max Series adjustable frequency drive
MN04020002E
For more information visit: www.eaton.com 45
February 2010
Table 11: All Parameters (continued)
PNU ID
Access
Right
RUN Designation Value Range
Factory
Setting
User
Setting
Communications
S2.1 808 — Communication
status
Format xx.yyy
xx = number of error messages
(0 – 64)
yyy = number of correct messages
(0 – 999)
0
S2.2 809 — Fault history 0 = field bus deactivated
1 = Modbus
0
S2.3 810 — Address (slave) 1 – 255 1
S2.4 811 — Baud rates 0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57600
5
S2.5 812 — Number of
stop bits
0 = 1 Stop bit
1 = 2 Stop bits
0
S2.6 813 — Parity type 0 = None (inaccessible) 0
S2.7 814 — Communication
status,
Timeout
0 = Not used
1 = 1s
2 = 2s
… 255s
0
S2.8 815 — Reset
communication
status
0 = Not used
1 = Reset value of parameter S2.1
0
Unit Counter
S3.1 827 — MWh counter MWh 0.00
S3.2 828 — Operation, days d 0
S3.3 829 — Operation, hours H 0
S3.4 840 — RUN, days d 0
S3.5 841 — RUN, hours H 0
S3.6 842 — RUN, meter 0