Installing Options and Accessories
5-8 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality
Table 5-4. Pull-Chain Wiring Terminations with MOBs
From To Function
UPS 1 CAN Bridge Card J3–1 (Alarm) MOB 1 Aux 1 NC
MOB Open Alarm
UPS 1 CAN Bridge Card J3–2 (Alarm Return) MOB 1 Aux 1 Com
UPS 1 TB2–1 (Pull Chain) MOB 1 Aux 2 NO Pull Chain
UPS 1 TB2–2 (Pull Chain Common) UPS 2 TB2–2 (Pull Chain Common) Pull Chain Common
UPS 2 CAN Bridge Card J3–1 (Alarm) MOB 2 Aux 1 NC
MOB Open Alarm
UPS 2 CAN Bridge Card J3–2 (Alarm Return) MOB 2 Aux 1 Com
UPS 2 TB2–1 (Pull Chain) MOB 2 Aux 2 NO Pull Chain
UPS 2 TB2–2 (Pull Chain Common) UPS 3 TB2–2 (Pull Chain Common) Pull Chain Common
UPS 3 CAN Bridge Card J3–1 (Alarm) MOB 3 Aux 1 NC
MOB Open Alarm
UPS 3 CAN Bridge Card J3–2 (Alarm Return) MOB 3 Aux 1 Com
UPS 3 TB2–1 (Pull Chain) MOB 3 Aux 2 NO Pull Chain
UPS 3 TB2–2 (Pull Chain Common) UPS 4 TB2–2 (Pull Chain Common) Pull Chain Common
UPS 4 CAN Bridge Card J3–1 (Alarm) MOB 4 Aux 1 NC
MOB Open Alarm
UPS 4 CAN Bridge Card J3–2 (Alarm Return) MOB 4 Aux 1 Com
UPS 4 TB2–1 (Pull Chain) MOB 4 Aux 2 NO Pull Chain
MOB 1 Aux 2 Com MOB 2 Aux 2 Com
Pull Chain CommonMOB 2 Aux 2 Com MOB 3 Aux 2 Com
MOB 3 Aux 2 Com MOB 4 Aux 2 Com