10.2.2 UPS Output
10.2.3 UPS Environmental
UPS Output Capacity 100% rated current
Output Voltage Regulation ±1.5% (10% to 100% load)
Output Voltage
(Nominal +/–3%)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content 1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See Table 3-7 or Table 3-8 for 480V three UPM models.
See Table 3-9 or Table 3-10 for 480V two UPM models.
See Table 3-11 or Table 3-12 for 415V three UPM models.
See Table 3-13 or Table 3-14 for 400V three UPM models.
See Table 3-15 or Table 3-16 for 380V three UPM models.
Output Voltage Balance 2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
±4° for 100% maximum load imbalance (linear load)
Output Transients Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation ±0.1 Hz free running
Synchronous to Bypass +10% to -10%
Frequency Slew Rate .7 Hz per second maximum
Load Compatibility 0.9 pF Leading
0.7 pF Lagging
Overload Capability 110% for 10 minutes
125% for 120 seconds
150% for 15 seconds
NOTE The 125% and 150% overloads are based on the non-derated hardware capability of the UPS.
Operating Temperature All ratings except 900 kW: 0 to 40°C (32 to 104°F) at elevation up to 1000m without
derating.
For 900 kW: 0 to 35°C at elevation up to 1000m without derating.
The recommended operating temperature is 25°C (77°F).
Operating Altitude Maximum 1000 m (3300 ft) at 40°C without derating
Storage Temperature –25 to +60°C excluding batteries (prolonged storage above 40°C causes rapid battery
self-discharge)
Relative Humidity (operating and
storage)
5% to 95% maximum noncondensing
Agency Markings 83 dB at a 1m distance, A weighted for one UPM UPS
83 dB at a 1m distance, A weighted for two UPM UPS
EMI Emissions and Immunity Meets IEC 62040-2, category C3
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage and with
no disturbance or adverse effect to the critical load.