Installing Options and Accessories
5-10 Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual
P-164000501—Rev 09 www.eaton.com/powerquality
Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations
Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring
Terminal TB1
Signal Connections
from the UPS
Ground
Terminal
Terminal TB3
120 Vac Power
UPS Can Card J3
120 Vac from
Critical Bus
(Customer
Supplied)
Line
Neutral
Twisted Pair
Ground Terminal
RMP II, RIM II, or SCM II
Table 5-5. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
To
RMP II, RIM II, or SCM II
Tightening Torque
Nm (lb in)
Remarks
J3–6 (TX) TB1–5 (RDX*) 0.9 (8)
Use twisted pair
J3–7 (TX) TB1–4 (RDX) 0.9 (8)
N/A TB3 Line 0.9 (8)
N/A TB3 Neutral 0.9 (8)
N/A Ground Terminal 2.7 (24) Maximum