EasyManua.ls Logo

Eaton Power Xpert 9395P-900 Series - Figure 4-5. Section Joining

Eaton Power Xpert 9395P-900 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS System Installation
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 4-7
Figure 4-5. Section Joining
5. Remove the screws securing the left top panel and remove the panel (see Figure 4-5). Retain the
hardware for later use.
6. Remove the screws securing the left middle panel and remove the panel (see Figure 4-5). Retain the
hardware for later use.
CAUTION
Use care during installation to protect components mounted on the right side of the ISBM section
and the intercabinet wiring harnesses attached to the left side UPM section from damage.
ATTENTION!
Lors de l’installation, prendre soin de protéger les composantes du côté droit du module de
contournement de système intégré (ISBM) et les faisceaux de câbles reliant les armoires du côté
gauche du module d’alimentation universel (UPM).
NOTE Clearance between the ISBM and the UPM sections must be less than 1/2” so that
joining brackets can be installed.
Left Top Panel
Wireway Panel
Left Middle Panel
Corner Channel
UPM Section
Interior Left
Side Panel

Table of Contents

Related product manuals