Chapter 10 Product Specifications
10.1 Model Numbers
The UPS is housed in two or three free-standing cabinets, divided into two or three sections with safety shields
behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings.
10.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2.1 UPS Input
The following sections detail the input, output, environmental, and battery specifications for the UPS.
Models Power Rating Frequency
Eaton 9395P-900/900* (three or four UPM) 900 kVA, 900 kW 50/60 Hz
Eaton 9395P-900/900 (three or four UPM) 900 kVA, 825 kW 50/60 Hz
Eaton 9395P-900/825 (three or four UPM) 825 kVA, 825 kW 50/60 Hz
Eaton 9395P-900/750 (three or four UPM) 750 kVA, 750 kW 50/60 Hz
Eaton 9395P-900/675 (three or four UPM) 675 kVA 675 kW 50/60 Hz
Eaton 9395P-900/600* (three or four UPM) 600 kVA 600 kW 50/60 Hz
Eaton 9395P-900/600 (two or three UPM) 600 kVA 550 kW 50/60 Hz
Eaton 9395P-900/550 (two or three UPM) 550 kVA 550 kW 50/60 Hz
Eaton 9395P-900/500 (two or three UPM) 500 kVA 500 kW 50/60 Hz
Eaton 9395P-900/450 (two or three UPM) 450 kVA 450 kW 50/60 Hz
Operating Input Voltage 480 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 3-7 or Table 3-8 for 480V three UPM models.
See Table 3-9 or Table 3-10 for 480V two UPM models.
See Table 3-11 or Table 3-12 for 415V three UPM models.
See Table 3-13 or Table 3-14 for 400V three UPM models.
See Table 3-15 or Table 3-16 for 380V three UPM models.
Reduced for Generator
Adjustable
Input Current Harmonic Content 3% THD at full load
Power Factor Minimum 0.99 at full load
Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage 480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A
Battery Shunt Trip 48 Vdc