UPS Maintenance
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 9-3
a. Remove one top screw and two bottom screws securing each UPM section front panel. Lift the panel
straight up to remove it from the panel hanger bracket at the top of the cabinet.
b. Remove one top screw and two bottom screws securing each ISBM section front panel. Lift the
panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
c. If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the
door open.
d. Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from
the cabinet.
e. Push the washed or new foam filters over the screw heads on the cabinet mounted studs until
seated against the cabinet.
f. Reinstall the UPM section front panels removed in Step a. and secure with the retained hardware.
g. Reinstall the ISBM section front panel removed in Step b. and secure with the retained hardware.
h. If opened, close the front door and secure the latch.