EasyManua.ls Logo

Eaton Power Xpert 9395P-900 Series - Page 71

Eaton Power Xpert 9395P-900 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09 www.eaton.com/powerquality 3-37
Table 3-28. Recommended DC Input Battery Disconnect Ratings – Separate Battery
UPS Model
Input Rating
(each UPM)
480V
Eaton 9395P-900/900*
Eaton 9395P-900/600*
800A
Eaton 9395P-900/900
Eaton 9395P-900/825
Eaton 9395P-900/750
Eaton 9395P-900/675
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
700A
NOTE Because of the future upgradability to a fully rated 900 kVA UPS with the addition of the
FI-UPM, these breaker sizes are specified for a 900 kVA UPS.

Table of Contents