Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 33
Table 8. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395-
1100/750, and 9395-1100/825 Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1070 892 1234 1029 1358 1132
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(6)
500
(5)
500
(6)
500
(5)
500
(6)
500
(5)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
938
782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(5)
500
(5)
500
(5)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
938
782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
DC Input from Each Battery Disconnect to
Each UPS UPM
(1) Positive, (1) Negative
C
Total Amps
551 551 551 551 551 551
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
938
782 1083 902 1191 992
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
UPS Installation Plan and Unpacking