INSTALLATION
EATON Powerware
®
9125 (9910-E30) UPS Installation Guide for IBM
®
Applications S 164201696 Rev 1
17
PDM Installation
To install t he optional FC 6570 PDM:
1. Verify that the bypass switch on the PDM is in the NORMAL
position (see Figure 24).
2. Select the input voltage (208 or 240V) using the Voltage Selector
Switch according to the utility voltage:
S Utility voltage 200–208V, select 208V
S Utility voltage 220–240V, select 240V
NOTE The output of the PDM is 120/240V while the UPS and utility inputs are 200–240V.
3. Verify that the power cord provided with the IBM equipment is
detached from the UPS input connector. Retain the cord for future
use.
4. Connect the jumper cable (provided in the PDM accessory kit) from
the 16A UPS output receptacle into the UPS-output connector on
the PDM.
5. Plug the attached PDM-to-UPS cord into the input connector on the
UPS rear panel.
Voltage Selector Switch
Output Receptacles
(Two L6-15R)
Bypass Switch
UPS-Output
Connector
PDM-to-UPS Cord
Output Receptacles
(Two 5-15R)
Input Connector
UPS Output Receptacle (16A, IEC 320-C19)
UPS Input Connector
(16A, IEC-320)
Power Cord
PDM
UPS
UPS Battery Connector
Output Receptacles
(Four 6-20R)
PDM Output Circuit Breaker
Figure 24. UPS and PDM Installation (FC 6570 PDM Model Shown)

Other manuals for Eaton Powerware 9125