OPERATION
EATON Powerware
®
9125 (9910-E30) UPS Installation Guide for IBM
®
Applications S 164201696 Rev 1
39
Table 13. Configuration Mode LEDs and Options
Bar Graph Indicators Option LED Status Explanation
230V Nominal Input
Voltage
On (default) Selecting this option changes the nominal input voltage
to 230V.
g
Flashing 230V is disabled; one of the other input voltage options is
selected.
220V Nominal Input
Voltage
On Selecting this option changes the nominal input voltage
to 220V.
g
Flashing
(default)
220V is disabled; one of the other input voltage options is
selected.
240V Nominal Input
Voltage
On Selecting this option changes the nominal input voltage
to 240V.
g
Flashing
(default)
240V is disabled; one of the other input voltage options is
selected.
Site Wiring Fault
Alarm
On (default) Alarm sounds when the polarity of the outlet is reversed
or the ground connection is missing; have a qualified
electrician repair the outlet wiring.
Flashing* Alarm DOES NOT sound when the polarity of the outlet is
reversed or the ground connection is missing.
* Site Wiring Fault is not available for 230V models;
Flashing is the default.
AC Input Failure
A
l
a
r
m
On (default) Alarm sounds when there is an AC input failure.
Alarm
Flashing Alarm DOES NOT sound when there is an AC input
failure.