2 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Standards and Certifications
UL 508
CSA 22.2/14-10
IEC 60947-4-2
CE Conformance
EMC Immunity
Immunity Severity Level
Electrostatic discharge
IEC 61000-4-2
8 kV air discharge
4 kV contact discharge
Electromagnetic field
IEC 61000-4-3
10V/m
80–1000 MHz
2 angles
Fast transient bursts
IEC 61000-4-4
2 kV, 5 kHz rep, 2 min. intervals
1.2/50 uS–8/20 uS surges
IEC61000-4-5
2 kV line to earth
1 kV line to line
1 minute intervals
Terminal connections 4 kV line to earth
2 kV line to line
1 minute intervals
Conducted RF
IEC 61000-4-6
10V rms
0.15–80 MHz
Radiated RF immunity
N 61000-4-3
10V rms
80 MHz–1 GHz
50/60 Hz magnetic field
IEC 61000-4-8
Meets requirements
Voltage dips interrupt
control power
30% dip at 10 ms
60% dip at 100 ms
100% dip at 5s
Emissions
Radiated EN 55011, Class A
Conducted EN 55011, Class A
www.comoso.com