EasyManua.ls Logo

Eaton S611 - Torque Settings and Corresponding Current Values

Eaton S611
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Fault occurrence categories
Immediately when START command is issued
During the START ramp, before the internal bypass
contactors close
During the internal bypass contactor closure event
Anytime during the RUN operation
During the STOP command
LED indication conditions
Fault
Active fault is present, cannot RESET
Ready
Not responding to START command from field wiring
LEVEL sense
Insufficient voltage at terminal “Permissive”
Insufficient voltage at terminal “Start”
EDGE sense
Cycle 24 Vdc at terminal “Start”
Insufficient voltage at terminal “Permissive”
Insufficient voltage at terminal “Start”
OFF—All
Check for loss of 120 Vac control power and/or less
than 100 Vac
Check terminal block for condition and security
Verify 120 Vac at appropriate terminals
Verify proper operation and capacity of CTs
START command troubleshooting
From the terminal block
Verify that terminal “Permissive” is energized
continuously
Verify that 120 Vac is applied to terminal “Start” to
issue START command
If terminals “Permissive” and “Start” are tied
together, verify that both terminals receive 120 Vac
START signal
If START control parameter is set to EDGE, verify that
120 Vac has been cycled (removed, then reapplied)
after faults have been reset
Torque Settings and Corresponding Current Values
Torque
Setting
Current as %
Locked Rotor Initial Motor Torque
85% 92% Maximum
71% 84%
56% 75%
45% 67% Default Value
36% 60%
33% 57% Wye-Delta Equivalent
27% 52%
19% 44% Minimum for Current Limit
14% 37%
9% 30%
1% 10% Minimum
www.comoso.com

Table of Contents

Other manuals for Eaton S611

Related product manuals