EasyManua.ls Logo

Eaton S611 - Setup and Starting

Eaton S611
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Operation of the user interface is broken into three modes listed across the top of the device.
Pressing the Mode key enables mode navigation.
Interface Mode Keys
The Mode and Protection/Operation (P/O) LEDs are used in conjunction to identify a selected
parameter.
Setup and Starting
Before You Begin
Be Aware of the Following:
1. The Permissive terminal must have 120 Vac applied to ENABLE starts.
2. To Start: Apply 120 Vac to the Start terminal while the Permissive terminal is energized.
3. To initiate a stop, remove the Permissive terminal input.
4. For two-wire control, jumper Permissive and Start terminal inputs together.
5. The Permissive and Network inputs must be energized (120 Vac) to enable starting of the
soft starter from the network.
6. After an overload trip, the S611 soft starter cannot be restarted until the prescribed
cool-down time has elapsed. Cycling control power does not reset the timer. If 120 Vac
power is removed, the soft starter will remember the remaining time and will resume the
cool-down timing when power is again reapplied.
Mode Description
Protection Used to set motor protection thresholds and/or disable protection parameters
Operation Used to set operational parameters, including auto reset modes
Monitoring Used to display run-time data parameters
www.comoso.com

Table of Contents

Other manuals for Eaton S611

Related product manuals