EasyManua.ls Logo

Eaton S611 - Existing Installations Checklist

Eaton S611
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Existing Installations Checklist
External circuit components issues
120 Vac control power undersized and/or failed
Isolation contactors open or damaged
Mains power faulty
Load disconnected
Load failure
Line/Load/Control circuits not restored after component
replacement
Verification of recent maintenance functions
All disconnected connections restored
Isolation devices restored to proper operating positions
Proper selection of replacement components
Verify suitability of added or modified components to
circuitry
Fault code verification
Use of test equipment to confirm/refute validity of fault
code
Determine if the fault can be reset
Determine if the fault is continuous or intermittent
Note operating conditions at time of fault if possible
Common fault codes
FC15—Power pole over temperature
FC31—Voltage imbalance
FC33—Jam
FC20—Overload
FC35—Temperature sensor
FC17—SCR not firing
FC18—Shorted SCR
FC21—Mains AC voltage loss
FC8—Voltage zero cross lost
General Information
120 Vac control power—terminal block connections
Run Enable 24 Vdc applied to terminal “Permissive”.
This 120 Vac input must be maintained continuously during
RUN
START Command enable from terminal block No
voltage applied to Network terminals. When a 120 Vac
signal is applied to the Network terminal, START control
from the terminal block will not be recognized
START Command with 120 Vac applied to terminal
“Permissive”, apply 120 Vac to terminal “Start”. The
signal requirement is momentary, but maintained is
acceptable. Terminals “Permissive” and “Start” may be
tied together for two-wire control START/STOP commands
STOP Command Remove 120 Vac from terminal
“Permissive”. Terminals “Permissive” and “Start” may be
tied together for two-wire control START/STOP commands
Wire size, minimum—14 AWG (single conductor) to all
terminal block connections. Wire should have no stands
missing or damaged during wire stripping. The use of
terminal ferrules is recommended to maintain connection
integrity
Control power supply requirements
Must meet or exceed steady state and inrush
capacity requirements
Steady state (sealed) A–D Frames = 85 VA, 120 Vac
Outrush A–D Frames = 600 VA, 120 Vac for 50 ms
minimum
Steady state (sealed) E–F Frames = 115 VA, 120 Vac
Outrush E–F Frames = 1200 VA, 120 Vac for 50 ms
minimum
Minimum supply voltage 120 Vac measured at the
terminal block
Maximum allowable voltage drop measured at the
terminal block = 5 Vac
www.comoso.com

Table of Contents

Other manuals for Eaton S611

Related product manuals