Setup
After all power and control connections have been made and you have read and understood the
different operating modes and protection features of the soft starter, set the Operations and
Protection parameters for your application. In many cases, only the Motor FLA parameter requires
adjustment to the proper value, and all other parameters may be used with the default values for
the initial Start. Review the Advanced Protection options of the S611 shown in Appendix B—
Protection and select the appropriate ones for your application.
Initial Configuration
1. The S611 Operation and Protection parameters may be edited using only 120 Vac control
power applied to 120 Vac Supply (TB1). Mains power is not required to edit and save
Operation and/or Protection parameters.
If any 120 Vac power source other than the normal system control power source is used to
power the control circuit to edit parameters, connections must be made in compliance with all
local, state, and national electrical codes.
2. In the Operation mode, set the operating parameters to the desired values. These settings
assume the motor has a 1.15 service factor.
Operating Parameters—Standard
Operating Parameter Units Min Max Default Notes
Motor FLA Amps Motor FLA parameter
must be set to motor
nameplate FLA to
achieve proper overload
protection
Frame Size A–52 26 52 26
Frame Size A–65 32.5 65 32.5
Frame Size A–77 38.5 77 38.5
Frame Size B–99 48 99 48
Frame Size B–125 62.5 125 62.5
Frame Size C–156 78 156 78
Frame Size C–180 90 180 90
Frame Size D–242 120 242 120
Frame Size E–302 151 302 151
Frame Size E–361 180.5 361 180.5
Frame Size F–414 207 414 207
Motor rated voltage Volts 200 600 480
Start method 0 2 0 0 = Voltage ramp
1 = Current limit
Start time Seconds 0.5 180 20
Initial torque % 0 100 45
Stop time Seconds 0 60 0
Kick start time Seconds 0 2 0
Kick start torque % 0 100 0
Auto reset mode 0 1 0 0 = Manual
1 = Auto
Advanced config N/A N/A N/A