68 S611 Soft Starter MN03902011E—May 2012 www.eaton.com
Modbus Map
Modbus
Coil Number
Modbus
Register Number R/W DCI Descriptor Notes
300 R DCI_MOTOR_CONTROL_STATUS
4785 R Run—bit 0
4786 R
4787 R In Bypass—bit 2
4788 R
4789 R
4790 R Fault—bit 5
4791 R
4792 R
4793 R
4794 R
4795 R
4796 R Relay 1—bit 11
4797 R Relay 2—bit 12
4798 R Control From Net—bit 13
4799 R Permissive—bit 14
4800 R
301 R DCI_ORION_CURRENT_SCALE_FACTOR Scale factor 10
302 R DCI_RMS_CURRENT_IA Amps * 10
303 R DCI_RMS_CURRENT_IB Amps * 10
304 R DCI_RMS_CURRENT_IC Amps * 10
305 R DCI_RMS_CURRENT_AVG Amps * 10
306 R DCI_RMS_VOLTAGE_VAB Volts
307 R DCI_RMS_VOLTAGE_VBC Volts
308 R DCI_RMS_VOLTAGE_VCA Volts
309 R DCI_RMS_VOLTAGE_AVG Volts
310 R DCI_TOTAL_KW kW * 10
311 R DCI_APPARENT_PF PF * 100
312 R DCI_POWER_SIGN
313 R DCI_FREQUENCY Freq * 100
314 R DCI_OVERLOAD_THERMAL_PILE Percent
315 R DCI_CURRENT_UNBAL_PERCENT Percent
316 R DCI_VOLTAGE_UNBAL_PERCENT Percent
317 R Reserved
318 R DCI_TEMP_POLE_1 Deg C * 10
319 R DCI_TEMP_POLE_2 Deg C * 10
320 R DCI_TEMP_POLE_3 Deg C * 10
321 R DCI_POLE_TEMP_AVG Deg C * 10
322 R DCI_NUMBER_OF_STARTS Reset though DCI_COMMAND_REGISTER
323 R DCI_RUN_TIME Hours, reset though DCI_COMMAND_REGISTER