Modbus Map
Modbus
Coil Number
Modbus
Register Number R/W DCI Descriptor Notes
— 300 R DCI_MOTOR_CONTROL_STATUS —
4785 — R Run—bit 0 —
4786 — R — —
4787 — R In Bypass—bit 2 —
4788 — R — —
4789 — R — —
4790 — R Fault—bit 5 —
4791 — R — —
4792 — R — —
4793 — R — —
4794 — R — —
4795 — R — —
4796 — R Relay 1—bit 11 —
4797 — R Relay 2—bit 12 —
4798 — R Control From Net—bit 13 —
4799 — R Permissive—bit 14 —
4800 — R — —
— 301 R DCI_ORION_CURRENT_SCALE_FACTOR Scale factor 10
— 302 R DCI_RMS_CURRENT_IA Amps * 10
— 303 R DCI_RMS_CURRENT_IB Amps * 10
— 304 R DCI_RMS_CURRENT_IC Amps * 10
— 305 R DCI_RMS_CURRENT_AVG Amps * 10
— 306 R DCI_RMS_VOLTAGE_VAB Volts
— 307 R DCI_RMS_VOLTAGE_VBC Volts
— 308 R DCI_RMS_VOLTAGE_VCA Volts
— 309 R DCI_RMS_VOLTAGE_AVG Volts
— 310 R DCI_TOTAL_KW kW * 10
— 311 R DCI_APPARENT_PF PF * 100
— 312 R DCI_POWER_SIGN —
— 313 R DCI_FREQUENCY Freq * 100
— 314 R DCI_OVERLOAD_THERMAL_PILE Percent
— 315 R DCI_CURRENT_UNBAL_PERCENT Percent
— 316 R DCI_VOLTAGE_UNBAL_PERCENT Percent
— 317 R Reserved —
— 318 R DCI_TEMP_POLE_1 Deg C * 10
— 319 R DCI_TEMP_POLE_2 Deg C * 10
— 320 R DCI_TEMP_POLE_3 Deg C * 10
— 321 R DCI_POLE_TEMP_AVG Deg C * 10
— 322 R DCI_NUMBER_OF_STARTS Reset though DCI_COMMAND_REGISTER
— 323 R DCI_RUN_TIME Hours, reset though DCI_COMMAND_REGISTER