Appendix A—Parameters
Parameter Lists
Operation Mode—Standard
Operating Parameter Units Minimum Maximum Default Notes
Motor FLA Amps Motor FLA parameter
must be set to motor
nameplate FLA to
achieve proper overload
protection
Frame Size A–52 26 52 26
Frame Size A–65 32.5 65 32.5
Frame Size A–77 38.5 77 38.5
Frame Size B–99 48 99 48
Frame Size B–125 62.5 125 62.5
Frame Size C–156 78 156 78
Frame Size C–180 90 180 90
Frame Size D–242 120 242 120
Frame Size E–302 151 302 151
Frame Size E–361 180.5 361 180.5
Frame Size F–414 207 414 207
Motor rated voltage Volts 200 600 480 —
Start method — 0 1 0 0 = Voltage ramp
1 = Current limit
Start time Seconds 0.5 180 20 —
Initial torque % 0 100 45 —
Stop time Seconds 0 60 0 —
Kick start time Seconds 0 2 0 —
Kick start torque % 0 100 0 —
Auto reset mode — 0 1 0 0 = Manual
1 = Auto
Advanced config — N/A N/A N/A —