S611 Soft Starter MN03902011E—May 2012 www.eaton.com 41
Advanced Operation Mode
Code Parameter Minimum Maximum Default Notes
P.00 Device Address Port 1 254 1 Port A—Top cover port
P.01 Modbus Baud Rate Port A 0 7 4 0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
P.02 Modbus Parity Port A 0 2 0 0 = Even (1 stop bit)
1 = Odd (1 stop bit)
2 = No parity (2 stop bits)
3 = Even (2 stop bits)
4 = Odd (2 stop bits)
5 = No parity (1 stop bit)
P.03 Device Address Port B 1 254 1 Port B —Hardwire port
P.04 Modbus Baud Rate Port B 0 7 4 0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
P.05 Modbus Parity Port B 0 2 0 0 = Even (1 stop bit)
1 = Odd (1 stop bit)
2 = No parity (2 stop bits)
3 = Even (2 stop bits)
4 = Odd (2 stop bits)
5 = No parity (1 stop bit)
P.06 User Interface Edit Lock 0 1 0 0 = UIM editing enabled (unlocked)
1 = UIM editing disabled (locked)
This is the only parameter that can be
edited when locked
P.07 User Display Parameter 0 10 0 Value displayed in TC LED
0 = Thermal capacity (%)
1 = Power factor
2 = Line frequency
3 = Residual ground current
4 = Voltage imbalance (%)
5 = Current imbalance (%)
6 = Run time
7 = Average pole temperature
8 = Pole temp A phase
9 = Pole temp B phase
10 = Pole temp C phase
P.08 Configuration Reset N/A N/A 0 1 = Power cycle
2 = Restore factory default parameters