42 S611 Soft Starter    MN03902011E—May 2012    www.eaton.com
Advanced Operation Mode, continued
Code Parameter Minimum Maximum Default Notes
P.09 Relay 2 (96, 97, 98) 0 1 0 0 = Faulted
1 = Not faulted
P.10 Relay 1 (13, 14) 0 5 2 0 = Faulted
1 = Not faulted
2 = Run (in bypass)
3 = Not in bypass
4 = Motor energized
5 = Motor not energized
P.11 Start Control (Level/Edge) 0 1 1 1 = Level
0 = Edge
P.12 Jam Trip Delay 1 20 2  —
P.13 Ground Fault Trip Enable 0  1 0  0 = Disable
1 = Enable
P.15 Ground Fault Trip Delay 1 20 2 Value in seconds
P.16 Ground Fault Start Delay 0 20 1 Value in seconds
P.17 Current Imbalance Trip Delay 1 20 5 Value in seconds
P.18 Current Phase Loss Trip Delay 1 20 2 Value in seconds
P.19 Under Load Trip Delay 1 60 5 Value in seconds
P.20 Under Load Source 0 1 0 0 = Trip on low kW%
1 = Trip on under current %
P.21 Under Voltage Trip Delay 1 20 10 Value in seconds
P.22 Over voltage Trip Delay 1 20 10 Value in seconds
P.23 Voltage Imbalance Trip Delay 1 20 10 Value in seconds
P.24 UI Comm Loss Fault Enable 0 1 1 0 = No fault on UI disconnect or comm loss
1 = Faulted
P.25 Shorted SCR Fault Enable 0 1 1 0 = Disable
1 = Enable
P.26 SCR Not Firing Fault Enable 0 1 1 0 = Disable
1 = Enable
P.27 Over Temperature Fault Enable 0 1 1 0 = Disable
1 = Enable
P.28 Overload on Start Enable 0 1 1 0 = Disable
1 = Enable
P.29 Command Register 0 3 0 0 = No action
1 = Clear motor run hours
2 = Clear motor start count
3 = Clear fault queue