S611 Soft Starter    MN03902011E—May 2012    www.eaton.com 21
Level or Edge Sensing
Level or edge sensing determines how the soft starter reacts 
to Start control commands after a fault trip has occurred. It is 
important to be aware if the Start command is a momentary 
or maintained signal. If the Start control signal is momentary, 
then either edge or level sensing may be selected and S611 
operation will be the same, as in either case only a 
momentary signal is placed on the start terminal of TB3. If 
the start control signal is maintained and edge sensing is 
selected, the signal must be removed, then reapplied to 
initiate a start.
Level Sensing 
Level sensing (default) is selected with the Start Control 
sub-parameter in the Advanced Config. menu. Level sensing 
means that the 120 Vac signal at the Start terminal may be 
continuous and does not require voltage to be removed and 
reapplied after a fault trip has occurred.
Level sensing will result in an automatic motor restart when:
●
All faults remain cleared or reset
●
The Permissive terminal is supplied with 120 Vac
●
The Reset Mode parameter is set to AUTO
●
There is 120 Vac power to the Start terminal (Start 
command—maintained)
Level sensing will allow a motor restart when:
●
All faults remain cleared or reset
●
The Permissive terminal is supplied with 120 Vac
●
The Reset mode parameter is set to AUTO or MANUAL
●
120 Vac power to the Start terminal is again applied 
(Start command—momentary)
This control configuration can be used where it is desirable to 
restart a motor after a fault without additional manual or 
automatic control. An example of this condition would be on 
a remote pumping station where it is desirable to 
automatically restart a pump after a power outage without 
operator intervention.
CAUTION
In the AUTO Reset mode, CAUTION must be exercised to
assure that any restart occurs in a safe manner.
Edge Sensing 
Edge sensing is selected with the Start Control 
sub-parameter in the Advanced Config. menu. Edge sensing 
means that the 120 Vac signal at the Start terminal must be 
removed (if maintained) and reapplied after a fault trip has 
occurred. If the Start signal is momentary, no further action is 
required to restart the motor. The cycling of 120 Vac power 
to the start terminal before starting is required regardless of 
the setting of the Reset Mode parameter. 
Edge sensing will allow a motor restart when:
●
All faults remain cleared or reset
●
The Permissive terminal is supplied with 120 Vac
●
The Reset Mode parameter is set to AUTO or MANUAL
●
120 Vac power to the Start terminal is reapplied (Start 
command—momentary)
Edge sensing will allow a motor restart when:
●
All faults remain cleared or reset
●
The Permissive terminal is supplied with 120 Vac
●
The Reset Mode parameter is set to AUTO or MANUAL
●
120 Vac power to the Start terminal is removed, then 
reapplied (Start command—maintained)
This control configuration can be used when restarting of the 
motor after a stop command or fault must be supervised 
manually or as a part of a control scheme. 
Auxiliary Relays 
Terminal block 2 (TB2) uses two (2) auxiliary relay functions 
to indicate status of S611 soft starter. 
1. Terminals 13 and 14 (Programmable)—At default setting, 
relay contacts use 120 Vac to provide bypass contactor 
status. The contact closes upon bypass and will remain 
closed until a stop is initiated or a fault occurs. The 
motor and load may continue to rotate after a stop is 
initiated if soft stop is being used or if the load inertia is 
high.
2. Terminals 96, 97 and 98 (Programmable)—At default 
setting, relay contacts use 120 Vac to provide fault or 
ready status indication. 
www.comoso.com